Product specifications
ARTICLE NUMBER | |
---|---|
60110102 | GI 3600 Compact Galvanic Isolation - transformer |
DIMENSIONS & WEIGHT | |
---|---|
Weight (Kg) | 28.6 |
Dimensions (HxWxD) | 380 x290 x 208 mm |
WINDING DATA | |
---|---|
Rated power | 3.6 kVA |
Rated voltage | 230 V / 110 V |
Rated frequency | 50 Hz / 60 Hz |
Nominal current | 16 A / 32 A |
Inrush current | Softstart included <4 A per unit |
Tappings | Prim/sec. mid-point (110 VAC) |
Material winding | Copper |
Temperature rise class | Class F 100 K |
Insulation class | Class H 180 C |
Insulation level | Class AC3 |
Impedance | Secundary less than 3.0% at 3.6 kVA |
GENERAL | |
---|---|
No load consumption | 21 W per unit |
Full load efficiency | >95% |
Ambient operating temperature | -10°C .. +45°C, derating to 80°C |
Storage temperature | -25°C to 85°C |
Operating humidity | 95% max, non-condensing |
Audible noise | <40.0 dB(A); <50dB(A) with forced cooling |
Local user interface | None |
PROTECTIONS | |
---|---|
Overcurrent, short circuit | Not included, external breaker(s) required according to local regulations |
Temperature protection | Automatic switch off if transformer core > 120°C |
Overvoltage protection | Softstart is protected for overvoltage using fuse |
Earthscreen between windings | Compliant to ABYC, can carry full fault current |
Safety | Standards IEC 60079, IEC 60726 |
MECHANICAL | |
---|---|
Protection degree | IP21 |
Connections input/output | 6 mm2 max. |
Cable gland entry | 22 mm |
Mounting holes | M8 |
Enclosure construction | Aluminum sheet metal |
Surface finishing | RAL9010 white + AE80104123621 black |