60201317 Front
60201317 Front

WPC 48 V / 6000 VA – 100 A

Product specifications

ARTICLE NUMBER
60201317WPC 48 V / 6000 VA - 100 A
TECHNICAL SPECIFICATIONS
Nominal battery voltage48 VDC
Continuous power @ 25°C5000 VA
Power 30 min. @ 25°C6000 VA
Power 5 sec. @ 25°C15000 VA
Maximum loadUp to short-circuit (fully protected)
Maximum a-symmetric loadUp to continuous power
Load detection (stand-by)2 to 25 W (AES) Automatic Enable System
Power factor0.1 - 1
Efficiency (@ full load)96 %
Consumption OFF / Stand-by / ON1.8 W / 2.3 W / 22 W
Output voltagePure sine wave 230 VAC (+/- 2%)
Output frequency50 Hz / 60 Hz (1) +/- 0.05% (crystal controlled)
Harmonic distortion (voltage)<2% THD
Overload and short-circuit protectionAutomatic disconnection with 3 time restart attempt
Overheat protectionWarning before shut-off with automatic restart
BATTERY CHARGER SPECIFICATIONS
Charge Characteristic6-step Bulk - Absorption - Floating - Equalization - reduced floating - periodic absorption. Number of steps, thresholds and return amps are completely adjustable.
Maximum charging current100 A
Temperature compensationWith Whisper temperature sensor WPC-BTS
Input voltage range150 to 250 VAC
Input frequency range45 to 65 Hz
Input current max. (transfer relay) / Output current max.50 A / 56 A
Transfer time<15 ms
MAIN SPECIFICATIONS
Weight42 kg
Dimensions H x W x D [mm]500 x 300 x 230
Protection degreeIP21
ColorRAL 9003
ConformityDirective EMC 2004/108/EC : EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022, EN 61000-3-2, 62040-2. Low voltage directive 2006/95/EC : EN 62040-1-1, EN 50091-2, EN 60950-1
Operating temperature range-20..+40°C, derating to 55°C
Relative humidity (operational)95% without condensation
Warranty2 years
Acoustic level<40 dB / <45 dB (without / with ventilation)
ACCESSORIES
60201032WPC-BUS cable 15 meter
60201030WPC auto start cable 15 meter
60201021WPC 24 VDC - 5 A slave charger (optional second slave charger to be 'build in' WPC)
40280101Touchpanel screen full color 7”