ARTICLE NUMBER |
60201302, 60201002, 60201312 |
WPC 24 V / 3500 VA (9000 VA max) 90 A - 230 V / 50-60 Hz |
MAIN SPECIFICATIONS |
Weight |
28 kg |
Dimension hxwxd [mm] |
510 x 330 x 150 mm |
Protection degree |
IP21 |
Color |
RAL 9003 |
Conformity |
Directive EMC 2004/108/EC : EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022, EN 61000-3-2, 62040-2. Low voltage directive 2006/95/EC : EN 62040-1-1, EN 50091-2, EN 60950-1 |
Operating temperature range |
-20..+40°C, derating to 55°C |
Relative humidity (operational) |
95% without condensation |
Ventilation |
Forced from 45°C |
Warranty |
2 years |
Acoustic level |
<40 dB / <45 dB (without/with ventilation) |
TECHNICAL SPECIFICATIONS |
Nominal battery voltage |
24 VDC |
Continuous power @ 25°C |
3000 VA |
Power 30 min. @ 25°C |
3500 VA |
Power 5 sec. @ 25°C |
9000 VA |
Maximum load |
Up to short-circuit (fully protected) |
Maximum a-symmetric load |
Up to continuous power |
Load detection (stand-by) |
2 to 25 W (AES) Automatic Enable System |
Power factor |
0.1-1 |
Efficiency (@ full load) |
94 % |
Consumption OFF/Stand-by/ON |
1.4 W / 1.6 W / 12 W |
Output voltage |
Pure sine wave 230 VAC (+/- 2%) |
Output frequency |
50 Hz / 60 Hz (1) +/- 0.05% (crystal controlled) |
Harmonic distortion (voltage) |
<2% THD |
Overload and short-circuit protection |
Automatic disconnection with 3 time restart attempt |
Overheat protection |
Warning before shut-off with automatic restart |