DC PowerCube 24 V – 150 A

Powerful electronically regulated switch – mode battery charger / power supply.

Connectable to our 1 / 2 / 3 Cylinder GENVERTER diesel generator. Second input shore / land power 90 – 264 VAC, 50 or 60 Hz. For 24 or 48 VDC batteries.

Request a quotation Where to buy
  • High efficiency (> 90%)
  • Easy installation (plug and play)
  • Can be paralleled with 2nd DC PowerCube (9 kW)
  • WhisperConnect (CANbus) connection

Product specifications

ARTICLE NUMBER
60202002 DC PowerCube 24 V - 150 A
DIMENSIONS & WEIGHT
Dimensions H x W x L [mm], Weight [Kg] 575 x 221 x 316, 21 Kg
GENERAL SYSTEM SPECIFICATIONS
Nominal battery voltage 24 VDC
Output current 0 - 150 A (short circuit protected)
Output voltage 26.5 / 28.5 VDC
Recommended battery capacity: 300 to 1500 Ah
Charge characteristic 3+ step charge characteristic
Slave charger 12 V - 20 A (3+ step charge characteristic) short circuit protected
INPUT SPECIFICATIONS
Grid input voltage range 90 - 264 VAC (45 - 65 Hz), (3 wire connection)
Grid input current Adjustable, from 2 A to 16 A
PM generator input range 80 - 300 VAC (30 - 500 Hz), (3 wire connection)
PM input current Adjustable, from 2 A to 14.5 A
Power factor (cos phi) > 0.85
Power Factor Correction (PFC) EN 61000-3-2
Temperature compensation -30 mV / °C
TECHNICAL SPECIFICATIONS
Supported battery types Open and sealed lead acid: Gel / Traction / AGM / Spiral and Lithium-ion
Battery leakage current <5 mA per battery
Charge voltages Bulk, Absorption, Float
Charge voltage AGM / GEL at 25°C 28.80 VDC, 28.50 VDC, 27.20 VDC
Charge voltage Traction at 25°C 29.20 VDC, 28.90 VDC, 26.50 VDC
Charge voltage Open lead acid at 25°C 28.50 VDC, 28.50 VDC, 26.50 VDC
Charge voltage Lithium ION at 25°C 28.80 VDC, 27.20 VDC, 26.50 VDC
Return current from absorption to float 6% of Imax
PowerCube status on/off Digital output (relay, two-way contact)
Failure Digital output (relay, two-way contact)
AC grid disabled Digital input (potential free input, closed is disabled)
PM input disabled Digital input (potential free input, closed is disabled)
Conformity Directive EMC 2004/108/EC : EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022,EN 61000-3-2, 62040-2 Low voltage directive 2006/95/EC: EN 62040-1-1, EN 50091-2, EN 60950-1
PROTECTIONS
PM input isolation protection Yes (open collector output 30 VDC, 100 mA)
Over temperature protection Yes, derating above 40°C, shutdown at high temperatures. (with automatic restart after cooling down)
Overvoltage protection (manual restart needed) 36 VDC + / - 0.5 VDC
Ingress Protection index IP21
MECHANICAL SPECIFICATIONS
Main battery connection 2 x M10 studs
Slave battery connection 1 x M5 stud
Earth grounding lug 1 x M6 stud
AC grid input 3 x M3 screw terminal block
PM grid input 3 x M3 screw terminal block
Remote control panel RJ12
Battery temperature sensor RJ12
Whisper Connect CANbus RJ45
Voltage sense Phoenix MSTB 2.5 / 2-ST-5.08
Digital outputs 6 x fastons (6.3x0.8)
Digital inputs 4 x fastons (6.3x0.8)
Operating temperature range -20 - 55°C (derating above 40°C)
Relative humidity in operation up to 95% without condensation
Ventilation Combined cooling (convection and forced (variable speed))
Acoustic level <52 dB
Warranty 2 years
Accessories Battery temperature sensor and remote control panel